NAPCO 704-9000D CONTROL ADJUSTMENTS

Free Autoclave Troubleshooting Guides





Yes, You Can Adjust the Temperature Control on Your NAPCO 704-9000D Autoclave

Just Follow The Directions Below


NAPCO 704-9000D Control Adjustments



Temp-Autoclave Control

The Temp-Autoclave Control may require adjustment. The function of this control is to maintain a maximum stabilized temperature of 132°C (270°F). The control requires calibration to assure that it is at the proper setting

To calibrate the control the following procedure should be followed:
  1. Check the water level and fill to gauge level
  2. Turn Function Switch to AUTOCLAVE ONLY. Turn Power Switch ON & Then Start The Timer
  3. Heat Unit to 132°C (270°F) by Adjusting the Temp-Autoclave Control Shaft
    • To gain access to the Temperature Control Shaft, remove the knob by loosening the two set screws. The slotted shaft can now be seen
    • Turn the shaft counterclockwise to raise the temperature. Turn clockwise to lower the temperature
    • Watch Temperature Gauge on door and adjust by 1/2 turn increments until temperature is reached
  4. Allow the unit to stablize. Watch the Temperature Gauge. The Temperature Light will flash off and on at intervals holding the temperature within tolerance
  5. Adjust as necessary during the stablization time. Temperature Light should flash on each time there is a 1° drop in temperature. When the unit has flashed several times the unit is stablized
  6. Place knob on temperature control shaft with indicator at position 7 and tighten both set screws
  7. Check operation of shaft and knob by turning to position 1 and back to position 7
Adjusting The Sensor

The sensor is set at the factory (near sea level) to close the Solenoid at 2°C above the boiling point of water. Since the boiling point of water will vary with altitude the Sensor may need adjustment when setting up the unit at higher elevations. Note the applicable temperature on the following chart..

BOILING TEMPERATURE OF WATER VS ALTITUDE
Altitude (Meters) Temperature °C Altitude (Feet) Temperature °F
0 100 0 212
150 99.5 1000 210.1
300 98.9 2000 208.3
600 97.9 3000 206.5
900 96.9 4000 204.6
1200 95.9 5000 202.8
1500 94.8 6000 201.0
2000 92.9 7000 199.3
  1. See Illustration Below
  2. Set Temperature Autoclave Control on Position 4, turn Power Switch ON and activate Timer (Check Water Level In Chamber Before Turning the Autoclave On
  3. Observe the temperature at which the Solenoid is activated. Listen for the first Click of the solenoid during warm-up
  4. If Sensor requires adjusment to 2°C above boiling point, locate adjustment screw at the end of the Sensor
    CAUTION: the terminal next to the adjustment screw is Electrically Hot. Use insulated screwdrive to make adjustment
  5. Turn the Power Switch OFF and allow the unit to cool for 10 minutes
  6. Repeat Step 1 above and observe the Temperature Gauge
  7. When the predetermined Temperature is obtained (2°C above local boiling point of water) turn Sensor adjusting screw counterclockwise until the Solenoid is activiated
  8. The autoclave should then be cooled and reactivated to activate the Solenoid again. This will confirm that the Sensor adjustment is now correct
Adjusting The Temperature Sensor Assembly on The NAPCO 704-9000D Autoclave


Click Here For A Larger Image


Cutaway View Of The NAPCO 704-9000D Autoclave


Click Here For A Larger Image

allclaveparts.com widget logo